Leave Your Message
Aluminum alloy Electromagnetic Shut-off Valver Shield Manufacturer JYFJS-011 Series
Valve

Aluminum alloy Electromagnetic Shut-off Valver Shield Manufacturer JYFJS-011 Series

Product Overview

 

The JYFJS-011 product of our company is used for emergency shut-off of gas pipelines and belongs to the category of gas emergency shut-off valves. It can be connected to gas alarm systems or fire protection and other intelligent terminal control modules to achieve automatic/manual emergency shut-off of the gas source, ensuring gas safety. The valve must be manually opened to meet safety handling standards and comply with gas incident handling requirements.

 

Application

 

This leak detector is widely used in the petroleum, chemical, environmental protection, metallurgy, refining, gas distribution, biochemical medicine, and agriculture industries.

    Working Principle and Structural Diagram
    JYFJS-011 (2)
    This valve is a normally open shut-off valve with a holding control mode. It remains open without power during normal operation and can automatically close upon receiving a shut-off signal. After closing, it can be manually opened and will automatically close again upon receiving another shut-off signal.

    When a leakage accident occurs, the alarm system sounds an alert, instantly providing a DC pulse voltage to the solenoid valve. The coil is energized, driving the valve to quickly close, cutting off the gas source and entering a self-locking state.

    When a gas leak occurs, the alarm's capacitor continuously releases a 3-second DC pulse voltage, energizing the coil, closing the valve to cut off the gas supply, and entering a self-locking state.

    The interaction of instantaneous electromagnetic force of the coil, permanent magnetic force, and spring force is used to achieve pulse drive, automatic valve closing, and manual valve opening self-holding functions.
    JYFJS-011 (3)
    Serial Number Area Name
    1 Valve body
    2 Diaphragm
    3 Valve cover
    4 Spring
    5 Actuator
    6 Reset Device
    7 Dust cover
    8 Moving iron core
    9 Sealing ring
    Product Model and Main Parameters
    JYFJS-011 (5)JYFJS-011-(5)
    JYFJS-011 (4)

    Nominal size

    DN15

    Model

    DRQF-15-0.1/KTLN

    (Aluminum straight-through valve)

    DRQF-15-0.01/KTLN

    (Aluminum angle valve)

    DRQF-15-0.1/KTLN

    (Copper straight-through valve)

    A(mm)

    60

    42

    60

    B(mm)

    28

    28

    27

    C(mm)

    85.5

    84.5

    85.5

    D(mm)

    99.5

    126.5

    99

    Connection method

    Rp1/2” internal thread (default), customized fittings are subject to the actual product.

    Rated flow (m3/h)

    1.8

    2.5

    1.8

    Weight (g)

    156

    173

    228

    Explosion-proof type Encapsulation type
    Mold Release Agent Nylon
    Explosion-proof marking Ex mb ⅡC T6 Gb
    Explosion-proof Certificate No. CQEx24.1641X
    Rated voltage (frequency) DC 12V pulse (capacitor discharge, 2A), continuous power-on time not exceeding 3s, interval time not less than 15s
    Permissible power short-circuit current 4A
    Power Static 0W, Operating 24W
    Protection level IP66
    Working medium Natural gas and other non-corrosive gases
    Maximum working pressure 0.01MPa, 0.1MPa (see nameplate for details)
    Opening method Manual opening
    Valve closing method Capacitor pulse drive/manual
    Ambient temperature -20(-40)℃~+60℃ (see specific model)
    Medium temperature -20(-40)℃~+60℃ (see specific model)
    Dielectric strength of solenoid valve 500V
    Encapsulation agent dielectric strength 4000V
    Cut-off time < 1 second
    Valve body material Aluminum alloy, copper alloy, customizable 304 stainless steel
    Sealing material Nitrile rubber
    Service life 10 years (typical value)
    Installation Diagram (Dimensions: mm)
    JYFJS-011
    1. There are two ways to close the valve when it is in the open state:
    ① Provide the solenoid valve with an instantaneous DC pulse power (DC12V pulse) for about one second, and the valve will close quickly.
    ② Press the red handle cap, the valve closes.
    2. The red handle above the marking line indicates the open state.
    3. When the valve is open, it may automatically close if subjected to strong vibrations, which is a normal condition.
    4. The electromagnetic coil (actuator) is detachable and can be removed or installed by rotating. Non-professionals are prohibited from disassembling or installing it.
    5. After the valve is shut off in an emergency, it must be manually checked and the fault cleared before resuming ventilation.
    6. When the valve is in the closed position, it can only be opened manually by pulling the red handle upwards.
    Unboxing and Inspection
    Standard accessories: Product manual (1 piece), factory inspection report (1 piece), product certificate (1 piece), mounting bracket (1 piece), installation accessories (1 piece).

    Unboxing inspection: The product appearance has no scratches, the label is intact and clear, and the accessories are complete.